Sole Agent Indonesia for Nickel Cadmium Batteries & Lead Acid batteries

    NIKSA Power Electronics, SAFT NIFE BICA IEC 60623 Nickel Cadmium Batteries, ULTRALEAD Lead Acid Batteries, Rectifier/ Battery Charger, Uninterruptible Power System.

    Customized Power Solution:  Oil & gas, petrochemical, communication, power generation, railway, military etc.

    Contact: PT Berjaya Indah Nusantara
    Address: Gedung Putra Kalimantan lantai 5 No 9, Jl Jend Gatot Subroto kav 12-13, Jakarta, Indonesia 12930. Phone: (62-21) 5222993, Fax: (62-21) 5252986. Email: ptbin[at]indosat[dot]net[dot]id .

    Factory: PT EnergitamaCatudaya
    Address: Kawasan Industri Jababeka, Bok K-7A, Cikarang Bekasi 17530. Phone: (62-21) 5250513, Fax: (62-21) 5222986. Email: energita[at]rad[dot]net[dot]id . Website: www.energitama.com

    3 Responses to “Sole Agent Indonesia for Nickel Cadmium Batteries & Lead Acid batteries”

    1. we require a turnkey job as follows. can you please spot a ups system supplier and nicad batt. to coooperate together for this project.

      BOOK OF TECHNICAL SPECIFICATIONS FOR

      SUPPLYING , ERRECTING, OPERATING OF

      (220 VDC UPS) 220 VDC BATT.CHARGERS,RECTIFIERS & NIC-CAD BATTS.

      1-OBJECTIVE:

      TO PURCHASE THREE BATT (CHARGERS,RECTIFIERS) AND THEIR RELATED BATTS. FOR REPLACEMENT OF OLD EXISTING GROUPS ACCORDING TO FOLLOWING SPECIFICATIONS:

      2-APPLICATION:

      POWER GENRATION

      3-SCOPE OF WORK

      SUPPLY, ERRECTION, CONNECTION, COMMISSIONING, TESTING AND PUT INTO OPERATION.

      4-BATT.CHARGER-RECTIFIER

      4-1.POWER SUPPLY THREE PHASE 400V + – 10%

      4-2.FREQUENCY 50HZ + – 5%

      4-3.OUTPUT VOLTAGE 220 VDC

      4-4.VOLTAGE REGULATION (FLOAT CHARGING) + – 1% OR BETTER AT THE FOLLOWING CONDITIONS :

      4-4-1.LOAD VARIATION 0-100%

      4-4-2.INPUT VOLTAGE + – 10% OR BETTER

      5-OUTPUT CURRENT 300-330 A , 100-150 A

      6-OUTPUT RIPPLE LESS OR EQUAL 1% RMS (BATT.OUT)

      7-EFFICIENCY 90% OR BETTER

      8-OUTPUT RELAY (OR EQUIVALNET) FOR EXTERNAL USE (RECTIFIER ON,OFF), OVER VOLTAGE, OVER LOAD.

      9-COOLING: NATURAL VENTILATION

      10-EXTERNAL PROTECTION IP40 OR BETTER

      11-EVENT LOG FOR BATT.AND CHARGER (AT LEAST 400 EVENTS)

      12-CHARGING : IU CHARGING ACCORDING TO DIN 41773 STANDARD OR EQUIVALENT

      13-PARALLEL OPERATION (TWO RECTIFIERS) FOR RECTIFIER (300-330A)

      14-PROTECTION: DC OVER VOLTAGE, ELECTRONIC CURENT LIMITATION, PHASE SEQUENCE.

      15-DISPLAY:

      15-1.MEASUREMENT:CHARGER OUTPUT VOLTAGE, CHARGER OUTPUT CURRENT, CHARGER INPUT VOLTAGE AC, CHARGER INPUT CURRENT AC, BATT.VOLTAGE, BATT.CURRENT.

      15-2.ALARM INDICATION (AT LEAST):

      NORMAL OPERATION, AC POWER SUPPLY FAULT, WRONG PHASE SEQUENCE, HIGH OUTPUT VOLTAGE, OVER LOAD, OVER VOLTAGE, UNDER VOLTAGE, CHARGING FAULT, BATT.DISCHARGE, FLOAT CHARGE , BATT.OK.

      16-NICAD BLOCK BATT. (STATIONARY)

      16-1. CAPACITY AT LEAST 550 AH FOR RECTIFIER (300-330A)

      16-2. CAPACITY AT LEAST 300 AH FOR RECTIFIER (100-150A)

      17-CLIMATIC CONDITIONS:

      OPERATING TEMP. 0-40C OR BETTER

      ALTITUDE:SEA LEVEL AT LEAST 30 METERS

      RELATIVE HUMIDITY MORE OR EQUAL TO 90% NON CONDENSATING

      18-MANUFACTURER MUST BE APPROVED BY AN INTERNATIONALY RECOGNIZED QUALTITY ASSURANCE OR STANDARDIZATION TO THE QUALITY MANAGEMENT SYSTEM STANDARD ISO 9001-2000, CERTIFICATE VALID AND APPLICABLE TO THE OFFERED MATERIALS AND EQUIPMENT (COPY OF CERTIFICATE INCLUDED IN OFFER).

      ALL DOCUMENTS (SPECIFICATIONS, DATA SHEETS, DRAWINGS, STANDARDS, OPERATING AND SERVICE MANUALS SHALL BE 5 COPIES IN ENGLISH

      THIRD PARTY INSPECTION FOR OFFERED EQUIPMENT MUST BE PROVIDED ON CONTRACTOR’S ACCOUNT, TO BE DONE BY INT’L RECOGNIZED INSPECTION AUTHORITY IN THE FACTORY. SCOPE OF INSPECTION MUST BE AGREED WITH BUYER.

      TRAINING PROGRAME IN FACTORY AND ON SITE TO BE INCLUDED

      19-TIME OF COMPLETION:

      180 DAYS SHIPPING ON FOB BASIS

      15 DAYS FOR ERECTION AND COMMISSIONING AS FROM HANDING OVER THE SITE TO CONTRACTOR

      20-REQUIRED QTY:

      TWO RECTIFIERS 300-330 A

      ONE RECTIFIER 100-150 A

      ========================THE END====================